+86 138 0000 0000 sales@zhouneng.top Reply within 12 hours (GMT+8)

FRP Round Counterflow Cooling Tower

CTR series · 5–800 m³/h · single-piece rotomolded shell · designed for rooftops and noise-sensitive sites.

CTI STD-201 FRP shell Low noise In stock models

Product overview

The CTR series is a counterflow tower with the fill pack directly above the fan-driven air stream. Water falls against rising air inside a seamless FRP shell, which gives a higher cooling efficiency per cubic metre than crossflow designs — so the unit is smaller for the same duty.

The shell, basin and louver frame are molded in one piece from isophthalic resin, so there are no panel seams to re-seal after five years in the sun. Fan stacks are interchangeable, which lets us swap a standard fan for a low-noise version without changing the footprint.

Flow rate
5 – 800 m³/h
Temperature drop
5 – 8 °C
Approach
4 – 5 °C
Max. inlet water
60 °C
Noise @ 15 m
≤ 65 dB(A)
Warranty
18 months

Typical lead time: 18–25 days for standard models, 30–40 days for low-noise or stainless options.

Design details

What makes the CTR hold its rating

01

Seamless rotomolded shell

One piece, no joints. UV-stabilized resin with a gel coat that keeps colour and impact strength after years outdoors.

02

Counterflow fill pack

PVC film fill at 0.38 mm with a self-cleaning profile. Higher thermal efficiency than crossflow at the same volume.

03

Low-noise fan option

Wide-chord aluminium blades and a slow-speed drive cut sound by 6–8 dB(A) with no loss of airflow.

04

Access without dismantling

Hinged louver panels and a side inspection door let a technician reach the fill and nozzles without a crane.

Model range

Nine standard sizes, all customizable

Ratings below are for 37 °C inlet / 32 °C outlet / 28 °C wet-bulb at sea level. Any model can be re-rated for your actual conditions.

CTR series — nominal performance
ModelFlow rateTemp. dropDiameterHeightFan motorOperating weight
CTR-5050 m³/h5 °C1,800 mm2,600 mm1.5 kW1,200 kg
CTR-8080 m³/h5 °C2,100 mm2,750 mm2.2 kW1,600 kg
CTR-100100 m³/h5 °C2,400 mm2,900 mm3.0 kW2,000 kg
CTR-150150 m³/h5 °C2,900 mm3,150 mm4.0 kW2,700 kg
CTR-200200 m³/h5 °C3,300 mm3,400 mm5.5 kW3,400 kg
CTR-300300 m³/h5 °C3,900 mm3,700 mm7.5 kW4,900 kg
CTR-400400 m³/h5 °C4,400 mm4,000 mm11 kW6,300 kg
CTR-500500 m³/h5 °C4,900 mm4,300 mm15 kW7,800 kg
CTR-800800 m³/h5 °C6,100 mm4,800 mm22 kW11,500 kg

Dimensions exclude the fan stack and inlet louver projection. Drawings are issued with every quotation.

Technical data

Construction & materials

ComponentStandardOptional
Shell & basinIsophthalic FRP, gel coatedVinyl ester for aggressive water
Fill mediaPVC film, 0.38 mmAnti-fouling / high-temperature fill
Drift eliminatorPVC, ≤ 0.01 % drift—
FanAluminium alloy, 4-bladeLow-noise wide chord
MotorIP55, Class F, 380–415 VIE3, 50/60 Hz, special voltage
DriveV-belt with tensionerGear reducer for ≥ 300 m³/h
Water distributionFRP header + ABS nozzlesStainless header
LouverFRP, hinged—
FastenersSS304SS316
Basin heater—Electric, for sub-zero climates
Operating limits

Design envelope

  • Inlet water temperature up to 60 °C
  • Design wet-bulb 20–32 °C (re-rated beyond)
  • Altitude correction applied above 500 m
  • Water quality: suspended solids ≤ 50 mg/L
  • Ambient operating range −20 °C to +50 °C
  • Electrical: 380/400/415/440 V, 50 or 60 Hz
CTI STD-201 ISO 9001 CE 18 mo warranty

Non-standard duties are quoted with a signed thermal calculation sheet, not an interpolated catalogue value.

FAQ

Questions buyers ask before ordering

How do I know which model I need?

Send us flow rate (m³/h), inlet and outlet water temperature, design wet-bulb, altitude and available footprint. We return a model number, a thermal calculation and a dimensioned drawing — usually within two working days.

What is the minimum order quantity?

One unit. For export orders we also quote spare fill, nozzles and a drive belt set, since a second shipment later costs far more than the parts.

Can the tower be shipped assembled?

Models up to CTR-200 fit in a 40HQ container fully assembled. Larger models ship as split shell sections with a bolted assembly kit and an illustrated site manual.

Do you provide installation support?

Remote supervision is included. An engineer can attend site for commissioning — travel and accommodation are quoted separately and typically cost less than a day of downtime.

What about spare parts after the warranty?

Fill, nozzles, eliminators, fans and belts stay available for at least 15 years. We keep the bill of materials for every serial number we ship.

Get a selection for your duty point

Two numbers and a wet-bulb are enough to start. We will come back with a model, a drawing and a price.

Request a Quote